Air is the only thing that travels through the whole plant without needing a door. It carries dust from raw-material receiving and steam from pasteurisation and evaporation, and if the airflow runs the wrong way, all the clean–dirty zoning work of Article 7 is undone. Article 8 chose the ceilings, walls and floors; Article 11 answers what the investor must settle before handing over the mechanical and electrical design: airflow rates, pressure differences between zones, filtration grades, condensation control and compressed-air purity.
Key points
- The EU requires mechanical airflow from contaminated areas to clean areas to be avoided; the US requires fans to be located so as to minimise contamination and steam to be controlled. Both require a design in which condensate does not drip onto food.
- High-risk zones are held at positive air pressure; design practice in Vietnam typically uses +15 to +30 Pa, 18–20 °C and 45–60% relative humidity for clean rooms.
- Condensation occurs when humid air meets a cold surface; the right ventilation reduces it, the wrong ventilation makes it worse. Where outdoor relative humidity is often above 80%, the moisture load of fresh air is the main design problem.
- Compressed air that touches food must be identified through HACCP and treated to a purity class stated explicitly under ISO 8573-1.
What the law requires of factory air
EU Regulation (EC) 852/2004, Annex II, Chapter I, point 5, requires food premises to have suitable and sufficient means of natural or mechanical ventilation; mechanical airflow from a contaminated area to a clean area is to be avoided; and ventilation systems must be built so that filters and other parts requiring cleaning or replacement are readily accessible. Point 2 of the same chapter requires the layout and design of premises to minimise air-borne contamination and to protect against the formation of condensation and undesirable mould on surfaces.
In the United States, Section 117.20(b)(6) of Title 21 of the Code of Federal Regulations (21 CFR) requires adequate ventilation or control equipment to minimise dust, odours and vapours, including steam, in areas where they may contaminate food; fans and other air-blowing equipment must be located and operated so as to minimise the potential for contaminating food, packaging materials and food-contact surfaces. Point (b)(2) names “air flow systems” as one of the means of separating operations in which cross-contamination is likely, and point (b)(4) requires that drip or condensate from ducts and pipes does not contaminate food.
As in Article 8, the law only states the result to be achieved. Which way the air flows, how large the pressure difference is and which filter grade is used are design decisions, and the investor should write those figures into the design brief rather than leave the M&E contractor to choose them.
Three objectives pulling in opposite directions
G.L. Quarini, author of the chapter “Heating, Ventilation, and Air Conditioning” in Handbook of Food Factory Design (2013), identifies three drivers of heating, ventilation and air conditioning in food plants: product safety and quality, a comfortable working environment for people, and energy saving. The three often conflict. According to Quarini, people feel comfortable at 16–27 °C, 45–60% humidity and CO2 below about 0.1%, whereas most fruit, vegetables and fresh meat keep best at about −1 to 4 °C. He argues that chilling the product locally and shortening its exposure to room air is usually cheaper than installing and running refrigeration for the whole production hall.
On airflow, a worker needs only about 0.2 l/s to breathe, but the supply air has to be much larger to dilute odours and toxic gases, hold temperature and humidity, and prevent condensation. The reference rate Quarini quotes for non-smoking offices is 10 l/s per person, or 1.4 l/s per square metre of floor where occupancy varies. Refrigeration and air conditioning account for about 10–20% of electricity consumption in most developed countries, so airflow must be calculated, not padded with arbitrary margins.
In Vietnam, energy use at production facilities is governed by the Law on Economical and Efficient Use of Energy No. 50/2010/QH12, as amended and supplemented by Law No. 77/2025/QH15 (effective from 1 January 2026). For workers, the permissible workplace microclimate values (temperature, humidity and air speed by type of work) are set by QCVN 26:2016/BYT, issued with Circular 26/2016/TT-BYT. HVAC design for a plant in Vietnam must therefore satisfy buyer hygiene requirements, the national microclimate regulation for workers and energy-saving targets at the same time.
High-risk zones, positive pressure and air filtration
P.J. Wallin, author of the chapter “Design Principles” in the same book, describes dividing the plant into low-risk and high-risk areas to control the movement of people, air and materials. A high-risk area is needed when the product is microbiologically sensitive, not naturally stable, has no kill step, or may be contaminated from other areas or from raw materials. Among the measures Wallin lists are changing clothes on entry, walls and floors that can be fully washed down, and a high positive air pressure in the room. Air supplied to clean rooms is commonly passed through HEPA filters; these need a high level of maintenance and regular replacement, so they must be installed where they are easy to reach.
Wallin gives no pressure-difference figures. Design practice for plants in Vietnam typically uses the values below, which the investor can take as a starting point for the designer’s proposal and then approve in writing:
| Parameter | Typical value | Purpose |
|---|---|---|
| Clean-room pressure relative to adjacent zone | +15 to +30 Pa | Air only flows from clean to dirty; keeps out fine dust and outdoor air |
| Clean-room temperature and humidity | 18–20 °C; 45–60% relative humidity | Prevents condensation on ceilings and floors, and mould |
| Supply-air filtration | HEPA retaining at least 99.97% of 0.3 µm particles | Removes dust, microorganisms and mould spores |
| Cleanliness class | Per ISO 14644-1, chosen by risk; for example class 5 locally at the aseptic filling zone | High cleanliness only where product is exposed after heat treatment |
Source: Compiled from plant design practice in Vietnam; Wallin (2013), sections 12.4.6–12.4.7.
On filter grades, Quarini notes that HEPA filters remove 95–99.999% of 0.3 µm particles, and that the higher the efficiency, the lower the permitted airflow and the higher the pressure loss, which means higher capital and running costs. Activated carbon is used to adsorb bad odours from decomposing organic matter. In AgrifoodV’s assessment, the investor should not specify HEPA for the whole plant but only for rooms where product is exposed after a kill step, because this item consumes fan power and replacement filters for the life of the project.
One constraint often overlooked in Vietnam: rooms that hold a pressure difference need tightly closed doors, while QCVN 06:2022/BXD on fire safety (with Amendment 1:2023) requires doors on escape routes to open easily in the direction of escape. Design practice in Vietnam resolves this with clean-room emergency doors fitted with self-sealing gaskets and electromagnetic locks interlocked with the fire alarm panel: in normal operation the door stays sealed and holds the pressure; when the alarm is triggered the lock releases so people can get out. This detail must be in the fire-safety design approval dossier, not left until commissioning.
Condensation: steam meets a cold surface
According to Quarini, condensation is a major problem in plants that handle chilled food. It occurs when humid air is cooled until the relative humidity at the coldest point exceeds 100%, typically on windows, poorly insulated walls or cold water pipes running through a warm, damp area. The book gives four remedies: reduce sources of water vapour, insulate cold surfaces, warm the room air, or increase the ventilation rate. It also warns that forced ventilation can reduce or eliminate condensation, but can also make it worse if the ventilation strategy has not been properly thought through.
A worked example in the book shows how quickly condensation arrives. A 500 m³ sauce production room runs during the day at 25 °C and 55% humidity; at the weekend production stops, the room cools by 1 K per hour, and the fan supplies only 20 m³/h of outdoor air. About 3.7 hours after cool-down begins, the inside surface of the window reaches 100% humidity and water starts to form. The same method allows the airflow or insulation needed to never reach the dew point to be calculated backwards.
In Vietnam the problem is harder because outdoor air often has humidity above 80%. Design practice in Vietnam shows that supplying fresh air directly into chill and frozen stores in the South is practically unworkable: the evaporators sweat, ice up and grow mould. In the North, North Central region and highlands, winter nights falling to 10–15 °C allow chill stores for fruit and vegetables to be pre-cooled through indirect heat exchangers, without bringing humid air into the store. The void above the ceiling must also have environmental control against condensation and be included in the cleaning and pest-control schedule, as noted in Article 8.
Air routing, fans and compressed air
Quarini notes that the power of a centrifugal fan rises with the cube of its rotational speed, while airflow changes almost linearly with speed; selecting an oversized fan and running it at full speed is therefore the most energy-intensive option. Air velocity is about 10 m/s in main ducts and about 20 m/s in high-velocity ducts, while in quiet areas it should stay at or below 3–4 m/s. In the book’s example, the pressure loss from air entering and leaving ducts and changing direction is about 18 times the friction loss, so duct routing matters as much as fan selection. Air curtains at doors can be effective but also increase air mixing and energy use. For complex layouts, the book considers computational fluid dynamics (CFD) may be the only self-consistent way to compare ventilation options.
Compressed air is the most underestimated utility. According to Wallin, compressed air is used to convey powders, mix, aerate, open and close valves and run packaging machines; where it comes into direct or indirect contact with food, this must be identified through HACCP analysis. The main contaminants are particles, water and oil, plus rust in the pipework and oil leaking from lubricated compressors. ISO 8573-1 classifies purity by these three groups; the edition must be stated because the particle limits of the 2010 edition differ from those of 2001. The book notes there is no legal definition of minimum cleanliness for compressed air used in food manufacture; the industry code Wallin cites corresponds to ISO 8573-1:2010 classes 1.2.1 for contact air and 1.4.1 for non-contact air. Design practice in Vietnam translates this into: contact air with a pressure dew point of −40 °C or lower, class 1 particle and oil filtration, an adsorption dryer and sterile filtration; non-contact air with a refrigeration dryer and a dew point of about +3 °C.
What companies should do
AgrifoodV recommends:
- Draw a pressure-zoning diagram for the whole plant on top of the zoning drawing from Article 7, with airflow arrows, and require the designer to state the pressure difference, temperature, humidity and filter grade for each room.
- Require the designer to calculate the fresh-air moisture load for the climate of the actual plant location, not climate data for temperate regions taken from foreign literature.
- Check on the drawings every point where steam meets a cold surface (ceilings over evaporation and pasteurisation, cold-store doors, chilled-water pipes) and the anti-condensation measure for each, linked to the finishes schedule from Article 8.
- Fix the compressed-air purity class under ISO 8573-1:2010 for each point of use in the tender documents, and include clean-room emergency doors in the fire-safety approval dossier.
AgrifoodV supports companies in developing the design brief, reviewing the M&E design scope and setting the design direction for processing plants.
The journey of building an export processing plant (11/29)
- Previous article: Article 10: Steam and energy systems: the foundation of every thermal process
- Next article: Article 12: Wastewater and solid waste: designed in from the start (planned for 25 November 2026)
References
- Quarini, G.L. “Heating, Ventilation, and Air Conditioning”, Chapter 16 in Baker, C.G.J. (ed.), Handbook of Food Factory Design. Springer Science+Business Media New York, 2013, pp. 403–425 (sections 16.2–16.3, pp. 404–407; 16.4.2 condensation, pp. 408–409; 16.5.3 CFD, p. 412; 16.8.1.1 condensation example, pp. 417–419; 16.8.2–16.8.4 air filtration, air conditioning, fans and ducts, pp. 419–422). DOI: 10.1007/978-1-4614-7450-0_16.
- Wallin, P.J. “Design Principles”, Chapter 12 in Baker, C.G.J. (ed.), Handbook of Food Factory Design. Springer Science+Business Media New York, 2013, pp. 297–326 (sections 12.4.6 high-risk area and 12.4.7 clean rooms, pp. 312–313; 12.6.7 compressed air, Tables 12.2–12.3, pp. 318–320). DOI: 10.1007/978-1-4614-7450-0_12.
- Regulation (EC) No 852/2004 of the European Parliament and of the Council of 29 April 2004 on the hygiene of foodstuffs, Annex II, Chapter I, points 2(a)–(b) and 5; consolidated version of 24 March 2021. eur-lex.europa.eu.
- 21 CFR 117.20 “Plant and grounds”, points (b)(2), (b)(4), (b)(6), Part 117 Subpart B (Current Good Manufacturing Practice), Electronic Code of Federal Regulations, up to date as of 13 November 2026. ecfr.gov.
- Law on Economical and Efficient Use of Energy No. 50/2010/QH12, as amended and supplemented by Law No. 77/2025/QH15 of 18 June 2025 (effective from 1 January 2026).
- QCVN 26:2016/BYT National Technical Regulation on Microclimate – Permissible Values of Microclimate in the Workplace, issued with Circular 26/2016/TT-BYT of 30 June 2016 of the Ministry of Health.
- QCVN 06:2022/BXD National Technical Regulation on Fire Safety for Buildings and Structures (issued with Circular 06/2022/TT-BXD) and Amendment 1:2023 (Circular 09/2023/TT-BXD), consolidated document No. 92 of the Ministry of Construction of 28 September 2026.
- Compiled from plant design practice in Vietnam (pressure differences, clean-room temperature and humidity, compressed air, hot and humid climate).
Article by AgrifoodV, compiled and interpreted from the sources above (accessed 17 November 2026). This content is not a substitute for design advice or legal advice for any specific project. Cover image: Jonathan Cooper / Pexels.